TM 5-194O-277-20
TM 1940-20/2
1.
Open access panel under control console (refer to paragraph 3-154).
2.
Using long nose pliers pull two connectors (1) loose from switch terminals (2).
3.
Set multimeter to OHMS X 10.
4.
One person connect multimeter probes (3) to switch terminals (2).
5.
Second person push switch in.
l
If meter reads other than 0 switch is good. Go to step 6.
l
If meter reads 0 switch is bad. Go to step 8.
Push connector (1) on terminals (2).
6.
7.
Close access panel (refer to paragraph 3-154).
Replace switch (refer to paragraph 3-47).
8.
3-103


 