Custom Search
 
  
 
TM 55-1905-219-14-10
5-32. GENERATOR (40 KW)-MAINTENANCE INSTRUCTIONS.
LOCATION
ITEM
ACTION
REMARKS
DISASSEMBLY (Cont.)
m. End frame
Pry straight out.
(15)
CAUTION
The exciter field is attached to the end frame, and the rotating rectifier assembly is
attached to the shaft. Protect the rotating rectifier assembly.
n. Screws
Remove.
(18) and
(19)
Remove.
field
assembly
(20)
NOTE
Check bearing (21) by turning the outer race with the fingers. If the bearing feels
rough, turns hard, or sticks in spots, replace the bearing. If the bearing needs
replacement proceed. If the bearing is good go to steps.
p. End frame
Remove.
center plug
(22), and
flatwashers
(23)
q. Screws
Remove.
(24), lock-
washers
(25), and
bearing
retainer
(26)
5-494


 