Custom Search
 
  
 
TM 55-1905-219-14-2
2-37. GENERATOR ENGINE - LOCAL START (Cont).
k.
When prolonged idling is needed, maintain at least 800 RPM minimum.
l.
Advance the throttle until the tachometer (13) indicates 1800 RPM.
m.
Assume control of the generator at the switchboard located in the engine access room.
NOTE
The voltage can be adjusted by rotating the manual control rheostat on the
switchboard located in the engine access room.
2-38. GENERATOR ENGINE - COLD WEATHER START.
Before starting engines, generator circuit breakers on control panel must be open.
a.
Perform all before operations on the Preventive Maintenance Checks and Services chart.
NOTE
Position all shut off valves open (counter-clockwise).
b.
Operate hand pump (1) on hydrostarter in forward engine room to charge accumulator (2 and 3).
c.
Pressure gage (4 and 5) should read:
AMBIENT TEMPERATURE
GAGE READING
Above 40 (4.4 )
F
C
1500 psi (1054.5 kg sq cm)
40 to 0 (4.4 to -17.8 )
F
F
C
C
2500 psi (1757.5 kg sq cm)
Below 0 (-17.8 )
F
C
3300 psi (2319.9 kg sq cm)
2-272


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business