Custom Search
 
  
 
TM 55-1905-219-14-2
2-42. STOPPING GENERATOR OPERATING - NON PARALLEL.
The following procedures applies to either generator #1 or generator #2 operating by itself (non-parallel).
a.
Reduce the load as mush as possible by placing circuit breakers on the power distribution panels in the OFF
position.
b.
Place the generator main circuit breaker (1 or 2) in the OFF position.
c.
Turn the voltage regulator rheostat (3 or 4) to decrease.
d.
Shut down the generator as per paragraph 2-43.
2-287


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business