Table 3-24. Generator Engine - Abnormal Engine Operation
Troubleshooting.
1. Uneven running or frequent stalling.
Step 1. Check for low coolant temperature.
Check the engine coolant temperature gage and, if the0temperature does not reach 16
0
185F (71to 85 C), while the engine is operating, consult the Abnormal Engine Coolant
to
Temperature Table 3-29.
Step 2. Check for insufficient Fuel.
Check engine fuel spill back and if the return is less than 0.8 gallons per minute with the
engine at 1200 RPM, consult the No Fuel or Insufficient Fuel Table 3-25.