TM 55-1905-220-14-2
2-41.
REMOTE OPERATION-GENERATOR #2 (Cont).
(2) Place generator #2/shore power voltmeter switch (2) in the GEN #2 position.
(3) Observe voltmeter (3). It should read 450V. If not, adjust the voltage adjust rheostat (4).
(4) Place the frequency meter switch (5) in the generator #2 position.
(5) Observe frequency meter (6). It should read 60 hz. If not, adjust the governor motor switch (7).
Shore power is being supplied to the vessel. Shore power indicator (8)
is lit and circuit breaker (9) is in the ON position.
(6) Place the shore power circuit breaker (9) in the OFF position.
NOTE
Shore Power indicator (8) will remain lit.
(7) When the generator is at 450V and 60 hz, place the generator #2 main circuit breaker (10) in the ON position.
(8) Place the distribution bus circuit breaker (11) in the ON position.
(9) Place the auto/manual switch (12) in the AUTO position.
NOTE
To start generator #2 from the switchboard, press switch (13). Shore
power circuit breaker (9) must be in the ON position.
To avoid the possibility of damage to the generator,  when  indicator
(8) is lit: Circuit breaker (9) must be in the OFF position, before placing
circuit breakers (10 and 11) in the ON position.