Custom Search
 
  
 
TM 55-1905-220-14-2
2-201. STARTING - PORTABLE FIRE PUMP (Cont).
(26)
to stop the pump - press and hold the STOP button (3).
If pump is operated for more than 15 to 20 seconds with the outlet valves (water outlet or three-
way-gate valve) closed,  the pump may speed up due to trapped air.  Open both valves
momentarily to let the trapped air escape.
b. To restart the fire pump while it is still warm, proceed as follows:
(1)
Pull the starter rope.
NOTE
Choking is not necessary.
(2)
If the engine does not start immediately, use the choke. Avoid flooding.
(3)
If the engine floods, proceed as follows:
(a)
Rotate the SLOW SPEED knob full clockwise.
(b)
Rote the HIGH SPEED knob full clockwise.
(c)
Pull the starter rope until the engine starts.
Do not refuel tank when engine is running.
2-822


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business