Custom Search
 
  
 
TM 55-1905-220-14-3
Table 3-25.
Generator Engine - No Fuel or Insufficient Fuel
Troubleshooting.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
Air leaks.
Step 1.
Check for low fuel supply. The fuel tank should be filled above the level of the fuel
suction tube.
Step 2.
Check for loose connections or cracked lines between fuel pump and tank or
suction line in tank.
Perform a Fuel Flow Test and if air is present, tighten loose connections and
replace cracked lines. Refer to paragraph 3-72.
NOTE
Fuel flow should be 0.8 gallons per minute with engine at 1200 RPM.
3-96


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business