Custom Search
 
  
 
TM 55-1905-220-14-3
Table 3-25.
Generator Engine - No Fuel or Insufficient Fuel
Troubleshooting (Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
Faulty installation (Cont).
Step 2.
Check for inoperative fuel return line - check lift
valve.
Make sure that the check valve is installed in the line correctly; the arrow should be
on top of the valve assembly or pointing upward. If the valve is inoperative,
replace with a new valve assembly. Refer to paragraph 3-70.
Step 3.
Check for high fuel return temperature.
Check the engine fuel spill-back temperature. The return fuel temperature must be
less than 150 (65.5C) or a loss in horsepower will occur. This condition may be
F
corrected by installing larger fuel lines or using the fuel oil heat exchanger.
3-100


 