Table 3-42.
Generator - Troubleshooting (Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
2.
Generator Noisy.
Step 1.
Listen for defective bearings.
a. Check oil level in sightglass - Add oil type OE/HDO.
b. Bad bearing - Refer to Direct Support Maintenance.
Step 2.
Check for damaged fan.
a. Inspect fan for cracks, breaks, insufficient mounting and looseness. Refer to
paragraph 3-63.
b. Inspect mounting of generator to engine - tighten bolts and refer to paragraph
3-62.
WARNING
Be sure generator is off. Tag switchboard to prevent accidental starting.
3.
No Output.
Step 1.
Check internal wiring - Burned, broken, worn or loose.
Tighten loose wire connection.
Insulate worn wires.
Refer all other problems to Direct Support Maintenance.
Step 2.
Inspect for defective external wiring.
Refer to Direct Support Maintenance.
3-126


 