Table 4-9. Air Conditioner System Noises - Troubleshooting.
NOTE
Refer to paragraph 4-29 and 4-30 for air conditioner and compressor
maintenance instructions.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. Compressor noises.
Step 1. Loose hold-down bolts.
Tighten bolts.
Step 2. Improperly aligned, loose or worn compressor drive:
a. Direct drive. Loose or misaligned coupling.
b. Direct drive. Loose coupling flange on compressor or motor shaft.
c. Belt drive. Loose, misaligned or worn belts.
d. Belt drive. Loose flywheel.
e. Belt drive. Loose motor pulley.
Realign, tighten or replace worn parts:
a. Realign coupling or tighten bolts.
b. Tighten setscrews. Replace key if worn.
c. Realign or adjust belt tension. Belt slack should be at the top. Replace
belts if worn.
d. Check flywheel nut, washer and key. Tighten or replace if worn.
Step 3. Insufficient clearance between piston and valve plate. (A sharp, medium pitched metallic
hammer is heard as a cylinder is unloaded.)
Replace over-tolerance parts.
Step 4. Motor or compressor bearings worn.
Replace worn bearings.