Custom Search
 
  
 
TM 55-1905-220-14-8
4-5. GENERAL (Continued).
Table 4-I0. Air Conditioner Capacity Control Troubles Troubleshooting (Continued).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step 4. Valve lifter mechanism defective. Lifter pins and springs do not retract below valve seats.
Remove cylinder heads and valve plates. Secure cylinder sleeves. Operate compressor
and by adjusting control valve check that lifter pins and springs retract below valve seats.
Remove cylinder sleeve and replace lifter parts, if defective. Remove sleeve, piston, and
connecting rod, and replace unloader power element, if defective.
5. Compressor noise varying with unloading.
Step 1. Valve lifter pins stuck.
Check and replace stuck lifter pins.
Step 2. Unloader power element piston stuck.
Repair or replace.
Step 3. Misaligned unloader power element fork.
Realign or replace.
Step 4. Leaking oil pressure line at connection to unloader power element.
Repair leaking line.
Step 5. Insufficient oil pressure. Increased and steady valve clatter when cylinder is unloaded.
Clean control oil strainer. Check and remove any other cause of low oil pressure.
6. Rapid unloader cycling.
Step 1. Partially plugged control oil strainer. '
Clean or replace strainer.
Step 2. Low oil pressure (less than 45 psi above suction pressure).
Clean control oil strainer. Check and remove any other cause of low oil pressure.
4-45


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business