Custom Search
 
  
 
TM 55-1905-223-10
(8)
Open FM-15, NO. 2 FIRE PUMP DISCH (15).
(9)
Open FM-10, FIREMAIN ISLN (6 ).
CAUTION
Do not turn an circuit breakers when no fire is present or valves have not been
properly aligned. Damage to pump could result.
(10) On Main Switchboard (FIGURE 2-101) set FIRE PUMP NO. 1 circuit breaker (1) and FIRE PUMP NO.
2 circuit breaker (2) to ON position.
(11) On Fire Pump Motor Controllers (FIGURE 2-102) set ON-OFF switch (1) to ON position.
(12) On Fire Pump Motor Switch (FIGURE 2-103), press START pushbutton (1) for both fire pumps.
(13) Open FM-23, STBD FOAM MONITOR ISLN (12).
(14) Open FM-24, PORT FOAM MONITOR ISLN (11).
(15) Open FM-11, FOAM STA 2 and PORT MONITOR ISLN (14).
(16) Open FM-12, FOAM STA 1 AND STBD MONITOR ISLN (13).
d. Foam Station.
(1)
Foam station operation. At foam station selected perform following:
(a) Ensure hose is connected to foam station isolation valve.
(b) Remove hose from hose storage rack.
(c) Extend hose to its full length.
(d) Ensure nozzle valve is closed.
(e) Open FOAM station isolation valve.
WARNING
Hold nozzle using a firm grip. If not held firmly, the nozzle will thrash about and
may cause serious personal injury.
(f) Direct nozzle at base of fire.
(g) Open nozzle valve.
2-322


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business