Custom Search
 
  
 
TM 55-1905-223-10
b. Air Conditioning.
NOTE
On High Voltage Air Conditioning unit set control switch to heater operation.
(1) Align Sea Water Cooling Piping System (FIGURE 2-108) as follows:
(a)
Open SW-1, SUPPLY TO PUMP (3).
(b)
Open SW-2, PRESSURE GAUGE SUPPLY TO STRAINER (4).
(c)
Open SW-3, PUMP SUCTION (5).
(d)
Open SW-4, PRESS GAUGE PUMP SUCTION (6).
(e)
Open SW-5, PRESS GAUGE PUMP DISCH (2).
(f)
Open SW-6, PUMP DISCH (8).
(g)
Open SW-15, SUPPLY TO PRESS SWITCH (20).
(h)
Open SW-17, SUPPLY TO AIR COND UNIT (17).
(i)
Open SW-18, DISCH FROM AIR COND UNIT (16).
(j)
Open SW-16 BY-PASS valve (18).
(k)
Open SW-28, OVBD DISCH FR AIR COND UNIT (21).
(1)
Open SW-7, SUPPLY TO AIR COND UNIT (24).
(m) Open SW-8, BY-PASS valve (22).
(n)
Open SW-13, ISLN-STBD STERN TUBE (11).
(o)
Open SW-11, SUPPLY TO STBD STERN TUBE (12).
(p)
Open SW-10, SUPPLY TO PORT STERN TUBE (13).
(q)
Open SW-12, ISLN-TO PORT STERN TUBE (15).
(r)
Open SW-14, ISLN-MSD (9).
(s)
Open SW-20, ISLN TO AIR COND UNIT (26).
(t)
Open SW-21, BY-PASS valve (27).
(u)
Open BB-35 SEACHEST VENT ISOLATION and BB-36 SEACHEST VENT.
(2)
At Auxiliary Machinery Motor Control Center (FIGURE 2-109), set A.C.S.W. COOLING PUMP circuit
breaker (1) to ON position.
2-333


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business