Custom Search
 
  
 
TM 5-1905-223-10
(2) Open LPA-18 SUPPLY TO STARTER (11).
NOTE
If the LCU is in beached condition, ship service diesel
generator will require its cooling system to be cooled from
seawater (SW) tank #8, either port or starboard.  When
starboard SSDG was aligned for fresh water cooling into SW-
8, cooling water flow for both generators is aligned.
d. On port Ship Service Diesel Generator and Control Panel (FIGURE 2-127) set IDLE-RUN switch (5) to
IDLE position.
(1) Set START-RUN-OFF switch (4) to START position.
(2) Press CRANK pushbutton (3).
CAUTION
If engine fails to start within 30 seconds, release CRANK
pushbutton.
(3) Allow engine to idle for 3 to 5 minutes until WATER TEMP gauge (2) needle starts to rise.
CAUTION
If OIL PRESS gauge (1) needle does not rise to 45 psi within
15 seconds, stop engine or equipment damage could result.
Notify unit maintenance.
NOTE
All diesel engines except main engines on the LCU have an
Automatic Low Oil Pressure Shutdown System. This system
will activate at a low oil pressure condition and shut engine
down.
(4) Set IDLE-RUN switch (5) to RUN position.
(5) On Main Switchboard (FIGURE 2-128), set AUTO OFF MANUAL switch (7) to AUTO POSITION.
(6)
On port Ship Service Diesel Generator and Control Panel (FIGURE 2-127), set EXCITATION-
SWITCH (6) to ON position.
(7)
On Main Switchboard (FIGURE 2-128), adjust GENERATOR 2 3PEED CONTROL (12) until
GENERATOR 2 FREQUENCY METER (10) indicates 60 Hertz.
(a) Set VOLTMETER SWITCH (15) to phase of generation on GENERATOR 2 VOLTMETER (8).
2-382


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business