Custom Search
 
  
 
TM 55-1905-223-10
Tunnel Watertight Door
Below Main Deck, Starboard Side, Watertight
Bulkhead 25
Tunnel Vent Watertight Closure (Aft P/S)
Below Main Deck, Watertight Bulkhead 25
Tunnel Supply Fan SF-3 Cover
Main Deck Weather Area (1-0-0-WEA), Port
Side, Bulwark, Frame 28
Air Cond. Unit Fire Damper No. 7
Emergency Generator Room, Port Side,
Above Emergency Switchboard
REMEMBER An actual fire emergency is not the time to train to
perform these procedures!
NOTE
The responsibilities to perform these space preparations
listed above have been identified on the LCU-2K station
bill for fire and damage control conditions and crew members
should routinely train for these responsibilities.
(4) Break Glass On FM-200 Pull Station. Initiate actuating the FM-200 fixed fire fighting
system for the Engine Room by breaking the glass for access to the pull handle.
Pull Stations are found in the following areas:
NOTE
Actual location may vary slightly between vessels.
(a) Engine Room Interior Remote FM-200 Pull Station located in the Passageway
(1-33-0-L), Main Deck Level, Frame 41.
(b) Engine Room Exterior Remote FM-200 Pull Station located on the Main Deck
Weather Area (1-0-0-WEA), Port Side, watertight bulkhead 28. This exterior
Watertight pull station requires first opening the watertight cover to expose the glass.
(5) Pull Lever On FM-200 Pull Station. Actuate the FM-200 system by pulling the handle. The
lever requires less than 40 pounds force and 6 inches of pull to operate. Allow no one to
enter the protected space until authorized to do so.
WARNING
In the event the FM-200 system electric horn/strobe or warning
lights (amber strobe) are activated, leave the protected space
immediately.
FM-200 is being released within 60 seconds, death or serious
injury could occur.
NOTE
Upon actuation of the FM-200 Fire Extinguishing System, a sixty
(60) second time delay before agent discharge will be experienced.
During this delay, FM-200 system electric horn/strobe will sound,
FM-200 warning bell will sound continuously and the FM-200
warning lights (amber strobe) will be illuminated.
Change 10
2-723


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business