WARNINGS
Actuation of the FM-200 System in the emergency discharge
mode will result in bypassing of the 60 second time delay and
pressure switches. The automatic equipment shutdowns, electric
horn/strobe, warning lights (amber strobe), and warning bell will
not function. FM-200 will be discharged immediately.
Operate the pressure switches by manually lifting the plunger
located on the top of the pressure switches to shutdown equipment.
Failure to observe these warnings could result in death or serious
injury.
To reduce temperatures within the protected space and manage
the risk of HF exposure to humans, the WWS is designed and intended
to be operated for a minimum of 15 minutes. This procedure should
be followed to the full extent or death or serious injury could occur.
NOTE
The engine room FM-200 system is augmented with an installed
WWS. If necessary, the FM-200 system could be used as a stand
alone system.
Operate the WWS for a minimum of fifteen (15) minutes. During the WWS operating
period, approximately every three (3) minutes, open valve WWS-2, Engine Room WWS
Strainer Blow Off for approximately ten (10) seconds. This will allow any foreign matter
to be flushed from the strainer basket.
c. Actuation Procedures, Tunnel FM-200 System. All fire scenarios and situations leading to the
decision when to actuate the FM-200 total flooding fire extinguishing system are not intended to be
discussed here. Refer to the US Army Fire Fighting Doctrine for guidance. However, the following
steps must be completed to effectively deploy the FM-200 system as designed.
In the event the FM-200 Fixed Fire Fighting System is to be actuated, the following steps must
be accomplished prior to actuation of the system.
WARNING
In the event the FM-200 System electric horn/strobe or warning
lights (amber strobe) are activated, leave the protected space
immediately.
FM-200 is being released within 60 seconds, death or serious
injury could occur.
(1) Evacuate All Personnel From Space. The Watch Officer or on-scene commander must
ensure all personnel have evacuated the space and are accounted for.
(2) Activate The Water Washdown System (WWS). In order to operate the WWS, the fire main
system must be charged. Ensure that the two (2) engine room fire pumps are placed on line
at the maximum operating pressure.
Change 10
2-725


 