Custom Search
 
  
 
TM 55-1905-223-10
7.6
Air Conditioning and Emergency Generator Room.
a.
Battery Charger:
Condition: Inspect damage and verify operational condition.
Standard: Undamaged and operational. ______________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
b.
Emergency Generator:
Condition: Verify serviceability, check operation in manual mode, trip main generator off line, emergency
generator should start and pick up load. Inspect oil pressure water temperature, verify speed control and
voltage regulation controls are functional. Inspect for leaks in lube oil, fuel oil, water and exhaust systems.
Check log for results of lube oil analyses, oil consumption and weekly functional test.  Check for
accomplishment of following PM services:
Annual:
Adjust valve lash clearance
Inspect drive belt
Check belt tensioning devise bearing
Check fan hub
Renew belt
Check turbo charger end play and inspect for oil leakage
Check/tighten mounting bolts
Check hoses
Check coolant heater
Remove and clean magnetic pick up.
Check generator winding heaters.
Bi-annual:
Clean cooling system and renew coolant
Change 8 G-47


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business