Troubleshooting - CONT
Table 2-2.
Malfunction
Test or Inspection
Corrective Action
BATTERY - CONT
STEP 2.  Check for dead cell.
Use a multimeter and check each cell.
MOTOR CONTROLLERS
201. No power.
STEP 1.  Check for open fuse.
Replace fuse, para. 2-223.
STEP 2.  Using a multimeter, check circuit breaker.
Replace circuit breaker, para. 2-223.
STEP 3.  Check for loose or broken electrical power cables.
Tighten or repair/replace broken electrical power cables.
POWER DISTRIBUTION PANELS
No power.
202.
STEP 1.  Check for open circuit breaker.
Reset circuit breaker.
STEP 2.  Check for loose or broken electrical power cable.
Tighten or repair/replace electrical power cables.
Using a multimeter, check for broken electrical power cable between
STEP 3.
main switchboard and power distribution panel.
Repair/replace electrical power cable.
Fluorescent, incandescent or floodlight does not work.
203.
STEP 1.  Check light bulb.
Replace burnt out bulb.
STEP 2.  Check circuit breaker at power distribution panel.
Reset circuit breaker.
Using a multimeter, check electrical power cables between power
STEP 3.
distribution panel and fixture.
Repair/replace electrical power cable.
2-156


 