Table 2-2.
Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
FIRE PUMP PIPING SYSTEM - CONT
STEP 3.  Check for air bound fire pump.
Open vent valve on pump casing until pump gains positive suction.
STEP 4.  Check for closed discharge pressure gauge cutout valve.
Open discharge pressure gauge cutout valve.
STEP 5.  Check for leaking lines fittings, or connections.
I n s p e c t all lines, tighten connections and fittings as necessary.
STEP 6.  Check for sticking valves.
Refer to POTABLE WATER PIPING SYSTEM troubleshooting Malfunction 1, Step 6.
STEP 7.  Check for leaking valves.
Refer to POTABLE WATER PIPING SYSTEM troubleshooting Malfunction 1, Step 8.
STEP 8.  Check for worn or defective pump.
Refer to PUMPS AND MOTORS troubleshooting.