TM 55-1905-223-24-18-1
Repair Ship Service Switchboard Current Transformers. (FIGURE 2-216)
2-295.
This task covers:
a. Disassembly, b. Repair, c. Assembly, d. Test.
INITIAL SETUP
Tools
Equipment Condition
Tool kit, electrician's,
Power to ship service switchboard OFF,
locked out, and tagged "Out of
Service - Do Not Operate."
Materials/Parts
Current transformer P/N 74R-251
Current transformer P/N 100R-102
Warning tags, Item 1, Appendix C
WARNING
Electrocution, serious injury, or equipment
damage can result from contact with live
e l e c t r i c a l  circuits.  Before beginning work
on electrical systems, ensure electrical
power is OFF, locked out and tagged to
prevent turn on during maintenance.
Remove bolt-on flat sheets (3, 4).
a.
b.
Tag and disconnect wiring to transformers (1, 2).
c.
Remove associated hardware and transformers (1, 2).
Repair to transformers is by replacement of transformers.