TM 55-1905-223-24-18-1
2-299. Repair Emergency Generator Switchboard Circuit Breakers.
This task covers:
a. Removal, b. Repair, c. Replacement, d. Test.
INITIAL SETUP
Tools
Equipment Condition
Tool kit, electrician's
Power to emergency generator
switchboard OFF, locked out, and
tagged "Out of Service - Do Not
Materials/Parts
Operate."
All switchboard circuit breakers OFF.
Circuit breakers P/N TEED136080
P/N THED136015
P/N TEC365C5050 with auxiliary
switch P/N TEDAS2B1-Rs and current
limiter, P/N TECL36050
being serviced.
P/N THED136100
P/N THED124C5015
Warning tags, Item 1, Appendix C
Electrocution, serious injury, or equipment
damage can result from contact with live
e l e c t r i c a l  circuits.  Before beginning work
on electrical systems, ensure electrical
power is OFF, locked out and tagged to
prevent turn on during maintenance.
Circuit breakers may have internally mounted
and factory installed accessories.
For disassembly of c i r c u i t breakers (1, 2, 3, 4, 6, 7 and 8, FIGURE 2-220) r e f e r
Refer to circuit breakers is by replacement.