Custom Search
 
  
 
TM 55-1905-223-24-18-2
REPLACEMENT
a. Carefully position fuel oil filter/separator on mounting foundation.
b. Install bolts (13), lockwashers (12) and nuts (11) to each of four legs (14) of unit. Tighten each nut to
a torque value of 250 ft-lb (339 N ).
m
c. Position gasket (17) and flange (18) assembly on inlet plate.
d. Connect flange assembly to suction piping at union elbow.
e. Install four bolts (19), lockwashers (16) and nuts (15) to secure flange (18) assembly to inlet plate.
There are no torque requirements.
f. Repeat steps c. through e. to install flange (3) assembly to outlet plate.
g. Position gasket (10) and flange (9) assembly on drain plate.
h. Connect flange assembly to drain piping at union (7).
i. Install four bolts (6), lockwashers (5) and nuts (4) to secure flange (9) assembly to drain plate. There
are no torque requirements
j. Close drain valve (8).
k. Open discharge valve. Remove tags.
WARNING
To prevent, injury to personnel, ensure that the ship's vent valve
is open and that a low pressure (10 psig or less) is used to fill
filter housing until all air has escaped.
l. Open suction valve. Remove tags.
m. Refer to initial start-up procedures in TM 55-1905-223-10 .
3-84


 