Custom Search
 
  
 
TM 55-1905-223-24-3
Table 1-1. Equipment Data - CONT
Characteristics
Reference Data
ELECTRICAL SYSTEM
Generator Assembly (Manufacturer-
Newage):
Rated at
250 kW, 240 volts, 3 phase, 60 Hz
rpm
1800
Power factor
0.8
Continuous at
122F (50C) ambient air temperature
Weight of generator only
1909 lbs (866 kg)
Manual voltage regular:
Connections required to the
generator
Exciter windings (X and XX)
Permanent magnet windings (P2, P3,
and P4)
Connections required to the
automatic voltage regulator
Exciter output (X and XX)
Permanent magnet supply (P2, P3,
and P4)
Starter motor, electric (STBD
engine only):
Maximum allowable resistance of
starting circuit with 24-volt
starter
0.002 ohms
STARTING AIR SYSTEM
Minimum operating pressure
60 psig
Maximum operating pressure
150 psig
1-12.  Safety, Care, and Handling.  Safety precautions must be observed at all times while performing
maintenance. General WARNINGS and first-aid data appear in the front of this manual. Review all safety
information before starting any task.  Carefully read through an entire maintenance procedure before
performing any maintenance function. Make sure the task can be done safely. All WARNINGS, CAUTIONS,
and NOTES are of great importance to your safety and the safety of the equipment.
1-9


 