Custom Search
 
  
 
TM 55-1905-223-24-3
(5) Remove all tags.
h. Connect the exhaust group air piping (paragraph 2-30).
i.
Connect the electrical wiring to the coolant heater group (paragraph 2-36). Remove tags.
j.
Ensure the following filters are secure:
(1) Fuel filters
(2) Full flow and bypass oil filters
(3) Water filter
k.
Connect all external wiring that was removed from the instrument panel, governor control, and r mote
e
sending units. Ensure that all connections are returned to the same locations from which they were
removed on the old engine. Remove tags.
l.
Remove the cover from generator terminal box.
m Refer to tags and notes made during the removal process and connect all cables and conduits to, and
through, the same locations on the generator terminal box that they were removed from on the old
generator set. Remove tags.
CAUTION
Ensure all leads are connected to their proper terminals to avoid
electrical component damage.
The center neutral or ground terminal is not to be used. If the
new generator comes equipped with a grounding strap, remove
the strap.
n. Refer to tags and notes made on removal and connect all leads to their proper terminals within the
terminal box. Remove tags. Replace the cover on the terminal box.
o. Remove the cover on the voltage regulator and return all external leads to the voltage regulator to their
proper terminals. Remove tags.
p. Install the voltage regulator and terminal box covers.
q. Connect the starter motor:
(1) Connect wiring and cables to electric starting motor/magnetic switch group (paragraph 2-25).
Remove tags.
(2) Connect air supply line to engine air starter (paragraph 2-24).
r.
Open the following external valves to the engine:
(1) Fuel supply line valve.
(2) Fuel tank return line valve.
Change 3 3-13


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business