TM 55-1925-273-10-1
0036 00
When the FM-200 system is actuated, pressurized CO2 from the system's actuating circuit closes the alarm system's pressure
actuated switch. These switches, in turn, energize the alarm system's strobe lights, horns, and bell. Once the alarm begins
sounding, the occupants of the engine room and AMS 1 have 60 seconds to evacuate the space prior to discharge of the FM-
200 fire suppression agent.
AMS 1
AMS 2
ENGINE
EMERGENCY
ROOM
ROOM
FM-200
PRESSURE
SWITCH
EMERGENCY GENERATOR
BATTERY CHARGER
-
PS-1A
+
EXTERIOR
MAIN
PANEL
DECK
BOX
120V MAIN DECK, 01 & 02
EMERGENCY LIGHTING
PANEL No. 1
B
FM-200
CIRCUIT
PRESSURE
JUNCTION
(CENTERLINE)
BREAKER 2
SWITCH
BOX 1
JUNCTION
BOX 2
PS-1
A
A
A
(PORT)
LEGEND:
A
(STARBOARD)
ALARM BELL
B
A
AMBER STROBE
A
LIGHT
ELECTRIC HORN
Figure 6. FM-200 Fire Suppression Alarm System Schematic
END OF WORK PACKAGE
00360036 00-7
00-7/8 blank


 