Custom Search
 
  
 
TM 55-1905-219-14-11
5-121.1 CONTACTOR (NEMA SIZE 3, 2, AND 3 POLE AC) - MAINTENANCE INSTRUCTIONS (Continued).
LOCATION
ITEM
ACTION
REMARKS
REPAIR (Cont)
d. Coil (10)
Pull straight out.
NOTE
If the magnet or armature requires replacement, proceed as follows
(if not proceed to step f.).
e. Magnet
Replace.
Replace armature
frame
(6), and magnet
clamp
frame (12) as an
(11),
assembly.
magnet
frame
(12),
and
spring
(13)
f.
Coil (10)
Install new coil with
terminal blades engag-
ing the coil terminal
clips .
g. Armature
Install narrow end to
(6),
the left into its
right
seated operating
pushbar
position.
(7) , left
pushbar
(8), and
springs
(9)
h. Clamp
Install.
plate (5),
indicating
plates
(4), and
screws (3)
i.
Cover (2)
Install.
and screws
(1)