2-37. GENERATOR ENGINE - LOCAL START (Cont).
h.
Release start button (9) as soon as engine starts.
i.
Observe oil pressure gage (11) on instrument panel (12). If no pressure is indicated within 10 to 15 seconds,
STOP. Check lubrication system. Minimum pressure is 25 psi (1757.7 gm sq cm) at 1200 RPM (13).
j.
Warm-up at part throttle, no load, for about 5 minutes before loading engine. Normal coolant temperature (14) is
160 , (71.1 ).
F
C
2-271
|
||