TM 55-1905-219-14-3
Table 3-23. Generator Engine - Hard Starting - Troubleshooting.
(Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
2. Low cranking speed.
Step 1. Check for improper lubricating oil viscosity.
Use the recommended grade of oil.
LUBRICATING OIL GRADES
DESCRIPTION
SPECIFICATION
OES (Sub Zero)
MIL-L-10295
OE/HDO - 10
MIL-L-2104
OE/HDO - 20
MIL-L-2104
OE/HDO - 30
MIL-L-2104
NOTE
At low ambient temperatures, use of a starting aid will reduce the cranking time.
Step 2. Check for loose hydrostarter connections or faulty starter.
Tighten the starter connections. Refer to tables 3-14 through 3-21 for
hydrostarter problems.
3. No fuel.
Step 1. Check for air leaks, flow obstruction, faulty fuel pump, and faulty installation.
To check for air leaks, flow obstruction, faulty fuel pump or faulty installation,
consult the No Fuel or Insufficient Fuel Table 3-4.
3-83


 