Tweet |
Custom Search
|
|
|
||
TM 55-1905-219-14-3
Table 3-43. Switchboard Troubleshooting (Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
2. Generator fails to supply power to switchboard, as shown on volt-
meter: It should read 450 VAC.
Step 1.
Check for loose, cut, broken, burned and worn
wiring.
Tighten or replace defective wiring. Refer to
paragraph 3-59.
Step 2.
in wrong position.
Place switch in Generator 2 position.
Step 3.
Check for defective voltmeter.
Refer to Direct Support Maintenance.
Step 4.
Check for defective voltmeter switch.
Refer to Direct Support Maintenance.
3. Generator fails to build up to rated voltage.
Step 1.
Check for incorrect adjustments.
Perform operating procedures.
Step 2.
Check for loose, cut, broken and worn wiring.
If connections are loose, tighten them. If wiring
is damaged, repair it. Refer to paragraph 3-59.
Step 3.
Check for defective voltage regulator.
Refer to Direct Support Maintenance.
Step 4.
Check for broken or damaged switches, meters, or
rheostats.
Refer to Direct Support Maintenance.
3-134
|
||