Table 3-43. Switchboard Troubleshooting (Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step 2.
Check for defective frequency meter.
Refer to Direct Support Maintenance.
Step 3.
Check for defective frequency meter switch.
Refer to Direct Support Maintenance.
8. Wattmeter fails to read.
Step 1.
Check for neon light visable in fuse holder.
Blown fuse, replace. Refer to paragraph 3-59.
Step 2.
in wrong position.
Place in Generator 2 position. If problem con-
tinues, refer to Direct Support Maintenance.
Step 3.
Check for defective wattmeter.
Refer to Direct Support Maintenance.
Step 4.
Check for defective fuse holder.
Refer to paragraph 3-59.
9. Shore power not available.
Step 1.
Check for shore power energized lamp not lit.
a.
Lamp loose in socket.
b.
Defective lamp. Replace. Refer to paragraph
3-59.
c.
Defective lamp holder. Refer to paragraph
3-59.
Step 2.
Check wiring.
Check or correct wiring from the source of power
to the Shore Power Box.
3-136
|
||