Custom Search
 
  
 
TM 55-1905-219-14-8
4-8.2.
FIRE PUMP - MAINTENANCE INSTRTUCTIONS. (Continued).
LOCATION
ITEM
ACTION
REMARKS
REASSEMBLY (Cont)
m. Screw
Tighten.
Tighten to 50
(10)
ft 1b (67.8 Nm).
n. Lock-
Crimp against one flat
Use vice grips-
washer
of screw (10).
do not use a
(8)
hammer.
o. Casing
Install on shoulder
gasket
of adapter (7).
(18)
p. Casing
Install on adapter (7).
(6)
q. Screws
Install.
(5)
r. Packing
Install and tighten.
gland
(25), and
nuts (15)
s. Screws
Install.
(4), and
nuts (3)
t. Screws
Install.
(2), and
nuts (1)
u. Motor
Rotate by hand and check
Correct any
shaft
for binding and rubbing.
binding and
(14)
rubbing con-
ditions.
v. Simplex
Perform service and fill
Refer to para
strainer
with water.
4-450


 