Custom Search
 
  
 
TM 55-1905-219-14-8
4-28. AIR CONDITIONING SYSTEM - MAINTENANCE INSTRUCTIONS (Continued).
(c)  The differential adjustment, inside the switch case, governs the cut-out point but does not
affect the cut-in point. Turning the differential screw clockwise widens the differential.
(d)  Recommended switch settings are given in paragraph 4-28a.
Proceed as follows to set switches:
1
Setting high pressure control switch.
a
Turn differential screw to minimum (counterclockwise) and range screw to high limit
(clockwise).
b
Start compressor and control discharge pressure by throttling condenser water flow.
c
Raise discharge pressure to about 10 psi (68.9 kPa) above cut-in point. Turn range screw
counterclockwise until contacts open, stopping compressor. When discharge pressure
drops to cut-in point, turn range screw slowly clockwise until contacts close, starting
compressor. The cut-in point is now set.
d
With the compressor running, turn differential screw (clockwise) to wide limit. Raise
discharge pressure to cut-out point and turn differential screw counterclock wise until
contacts open, stopping compressor. The cut-out point is now set.
e
Control discharge pressure and check switch settings and operation.
2
Setting low pressure control switch.
a
Turn differential adjustment clockwise to maximum position and range screw
counterclockwise to low limit.
b
Start compressor and control suction pressure by throttling the compressor suction stop
valve.
4-860


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business