Custom Search
 
  
 
TM 55-1905-219-14-9
4-45.3. CYLINDER ASSEMBLIES - MAINTENANCE INSTRUCTIONS. (Continued)
LOCATION
ITEM
ACTION
REMARKS
TEST
4. Cylinders
a. Weigh all cylinders upon receipt and every six months
thereafter, to insure no abnormal leakage. This includes
installed cylinders.
WEIGHTS
HALON 1301
NOMINAL EMPTY
NOMINAL CHARGED
CYLINDER & VALVE
FILL
RANGE
WEIGHT
WEIGHT
MIN FILL MAX FILL
KG
LBS
KG
LBS KG LBS KG
UNITS
LBS
AFT & FWD ENG RMS
80-125 36-57
88
40
168
77
213
97
FLAMMABLE LIQUID STRM21-40
10-18
57
26
78
35
97
44
b. To prepare cylinder for weighing, proceed as follows: