5-112. RUDDER ANGLE TRANSMITTER - MAINTENANCE INSTRUCTIONS
(Continued).
LOCATION
ITEM
ACTION
REMARKS
ADJUSTMENT (Cont)
g. Synchro
Rotate in either
This is the
direction until meter
approximate
reads approximately 37
zero setting.
VAC.
h. Power
Turn off at source.
i.
Jumper
Remove from terminals
wire
10 and 13.
j.
1. Disconnect.
2. Reconnect to terminals
11 and 13.
3. Place on low AC scale.
k.
Power
Turn on at source.
l.
Turn slowly until a
Null should be
null (minimum reading)
less than 0.25
is indicated on meter.
volt Rms.
m. Power
Turn off.
n. Screws (6)
Tighten.
and lock-
washers
(7)