2-90. FIRE PUMP - BILGE DRAINING - SHUTDOWN (Cont).
c. Aft Engine Room.
(1)
Check that flow control valve (7, FO-46) lever is on the off position.
(2)
Clean the simplex strainer as follows:
(a) Loosen yoke screw (8).
(b) Remove bolts (9), yoke (10), cover (11), and gasket (12).
Wear eye protection when using compressed air.
(c) Remove strainer (13), clean with clear water and dry with compressed air.
(d) The strainer can be drained by removing pipe plugs (14).
(e) Replace pipe plugs (14), strainer (13), gasket (12), cover (11), yoke (10), and bolts (9).
(f) Tighten yoke screw (8).
(3)
Place flow control valve (7, FO-46) lever in the on position .
(4)
The fire pump is now available for fire fighting.