Tweet |
Custom Search
|
|
|
||
TM 55-1905-220-14-2
2-112. AIR CONDITIONING SYSTEM START-UP (Cont).
(e)
Rotate the compressor suction stop shut-off valve (13)slowly clockwise until the proper
compressor suction pressure is reached.
If the compressor starts knocking, or the compressor suction gauge continues to fluctuate, STOP the
compressor immediately, and rotate the compressor suction stop shut-off valve (13) clockwise. Wait
five minutes and attempt a restart, with the compressor suction stop shut-off valve (13) partially open.
(29)
Check the following gages:
Compressor Suction Temperature (22) - 65 (17.8 ).
F
C
Compressor Suction (21) - 80 to 100 psi (551.6 to 689.5 kPa).
(30
Rotate the compressor suction stop shut-off valve (13) full counter-clockwise.
(31)
Check the lube oil pressure gage (23). The pressure should be 20 to 55 psi (137.9 to 379.2 kPa).
(32)
Check the sea water cooling pressure gage (24). The pressure should be 70 to 5 psi (482.6 to 517.1
7
kPa).
2-592
|
||