TM 55-1905-220-14-3
Table 3-27.
Generator Engine - Excessive Crankcase Pressure
Troubleshooting (Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
Cylinder blow-by (Cont).
Step 2.
Check for damaged piston or liner.
Inspect the piston and liner and replace damaged parts. Refer to paragraph 3-96.
Step 3.
Check for piston rings that are worn or broken.
Install new piston rings. Refer to paragraph 3-96.
2.
Breather restriction.
Step 1.
Check for obstruction or damage to breather.
Clean and repair or replace the breather assembly. Refer to paragraph 3-73.
3-103


 