Custom Search
 
  
 
TM 55-1905-220-14-3
Table 3-43.
Switchboard Troubleshooting.
WARNING
HIGH VOLTAGE
is used in operation of this equipment.
DEATH ON CONTACT
may result if safety precautions are not observed. Remember 450 volts in a salt
water atmosphere can be deadly. There are three potential sources of power:
Generator 1, Generator 2, and Shore power.
Place warning tags (red) on generator instrument panels on the forward and aft
engine room, to prevent accidental starting of generators.
NOTE
Prior to starting troubleshooting the switch board and generators, perform the
operating procedures in paragraph 2-35. When a problem occurs, consult this table
for a possible solution after observing the front panel meters.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
Starter cranks generator but stops when start switch is released.
Step 1.
Check for defective start solenoid.
Replace. Refer to paragraph 3-52.
Step 2.
Check for defective start switch.
Refer to Direct Support Maintenance.
3-127


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business