Tweet |
Custom Search
|
|
|
||
TM 55-1905-220-14-8
4-30. COMPRESSOR - HVAC - MAINTENANCE INSTRUCTIONS (Continued).
LOCATION
ITEM
ACTION
REMARKS
SERVICE (Cont)
e.
Strainer Insert.
(29)
REMARKS
When replacing strainer, insure that bail is compressed by manifold cover plate when plate is in
position. If bail is too short, grasp sides of bail so as to elongate it sufficiently to be compressed by
cover plate. Insure that strainer is positioned so that bail fits between two bosses on inside of cover
plate and thus is restrained from turning.
NOTE
Remove temporary felt sock filter installed inside suction strainer after 50 hours operation. If felt sock
is quite dirty, clean it and replace it for another 50 hours. Clean suction strainer whenever felt sock is
removed.
Temporary Suction (Felt) Filter
f.
Gasket (27
Install.
Torque to 50 to
and 28),
60 lb. Ft
suction service valve
(26), and screws (25)
NOTE
If this suction service valve is to be replaced. Unscrew valve from pipe
adapter.
4-919
|
||