Electric Fire Pumps (2):
Condition: Conduct operational test of pumps, inspect output streams from two fire hoses lead out on
uppermost deck, activate wash down systems and observe discharge from washdown nozzles. Observe pump
pressure with discharge valve closed. Conduct operational test of foam system by discharging foam from pilot
house top fire monitors. Inspect fire pumps during tests for excessive vibration or noise. Inspect all fire system
piping while under pressure for leaks in piping flanges, valves and fittings. Verify operation of fire pump remote
start switches.
Standard: Each pump is capable of discharging two streams of water at least 40 feet from hoses connected to
stations on the upper deck. Each pump is capable of maintaining 125 psi under closed discharge valve test.
Wash down system valves are operational, and system is leak free. All washdown nozzles discharge a uniform
spray pattern and quantity of water. Foam system is operational. Fire pumps operate without excessive noise
or vibration. Entire fire fighting piping system is leak free. Remote fire pump start stations are operational.
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
z.
Bilge and Ballast Pump:
Condition: Verify unit is operational by activating and pumping sea water overboard. Inspect pump and piping
system for leaks. Inspect pump for vibration and noise.
Standard: Unit is operational pumps a strong stream of water from overboard discharge. Pump and piping
system are leak free. Pump operates without excessive vibration or noise. ___________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
aa.
Sound Powered Telephone:
Condition: Inspect for condition of cabinet, bell and instrument.
Standard: Cabinet intact and serviceable, no indication of leakage, instrument and cord and bell present intact
and not damaged or deteriorated. ___________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________