TM 55-1905-223-24-12
Section IV. REMARKS
FIRE PUMP SYSTEM
REFERENCE
CODE
REMARKS
A
SEMI-AINNUAL:
CHECK ALIGNMENT OF PUMP AND ENGINE. SHIM UP IF NECESSARY. IF
MISALIGNMENT OCCURS FREQUENTLY, INSPECT THE ENTIRE PIPING SYSTEM.
UNBOLT PIPING AT SUCTION AND DISCHARGE FLANGES TO SEE IF IT SPRINGS
AWAY THEREBY INDICATING STRAIN ON THE CASING. INSPECT ALL PIPING
SUPPORTS FOR SOUNDNESS AND EFFECTIVE SUPPORT OF LOAD.
ANNUAILY:
REMOVE THE ROTATING ELEMENT. INSPECT THOROUGHLY FOR WEAR, AND
ORDER REPLACENT PARTS IF NECESSARY
CHECK WEARING CLEARANCES.
B
THIS ITEM IS NOT A CANDIDATE FOR DIRECT EXCHANGE WITH THE VENDOR.
Change 1 B-7/(B-8 blank)