Tweet |
Custom Search
|
|
|
||
TM 55-1925-273-10-1
0032 00
When the FM-200 system is actuated, ventilation to and from the engineering spaces, the ship's service diesel generators,
and the bow thruster and pump drive engines are automatically shut down to prevent FM-200 gas from being extracted
from the spaces. When a FM-200 pull box is actuated, horns sound, strobes flash, and the FM-200 alarm bell sounds to
alert personnel to evacuate the space. A 60-second delay is provided before the FM-200 agent is released to allow evacu-
ation of the engineering spaces.
3
AMS 2
PORT ENGINE
AMS 1
CONTROL ROOM
ENGINE ROOM
STBD ENGINE
SEE DETAIL B
2
1
DETAIL B
Figure 2. FM-200 Component Locations (Bilge Systems)
0032 00-2
|
||