TM 55-1925-273-10-1
0034 00
Table 1. Main Switchboard Interlocks
NOTE
The following interlock conditions occur when the SSDG 1, SSDG 2, or shore power is feeding
the main switchboard, the main bus tie is closed, and the FEEDBACK switch is in the NORMAL
position:
Circuit Breaker Closed
Cannot Close
SSDG 1 Circuit Breaker
Shore Power Circuit Breaker
SSDG 2 Circuit Breaker
Shore Power Circuit Breaker
Shore Power Circuit Breaker
SSDG 1 Circuit Breaker
Shore Power Circuit Breaker
SSDG 2 Circuit Breaker
Main Bus Tie Circuit Breaker
EDG Circuit Breaker
(Emergency Switchboard)
1S/E Bus Tie Circuit Breaker
2S/E Bus Tie Circuit Breaker
2S/E Bus Tie Circuit Breaker
1S/E Bus Tie Circuit Breaker
NOTE
The following interlock conditions occur when the Emergency Diesel Generator is running, and
the FEEDBACK switch is in the NORMAL position:
Circuit Breaker Closed
Cannot Close
EDG Circuit Breaker
Main Bus Tie Circuit Breaker
(Emergency Switchboard)
NOTE
The following interlock conditions occur when the EDG is running, and the FEEDBACK switch
is in the FEEDBACK position:
Circuit Breaker Closed
Cannot Close
EDG & Main Bus Tie Circuit Breaker
SSDG #1 Circuit Breaker
(Emergency Switchboard)
EDG & Main Bus Tie Circuit Breaker
SSDG #2 Circuit Breaker
(Emergency Switchboard)
EDG & Main Bus Tie Circuit Breaker
Shore Power Circuit Breaker
(Emergency Switchboard)