Custom Search
 
  
 
TM 55-1925-273-10-1
0069 00
5.
Align the emergency diesel generator for automatic start.
NOTE
Ensure that fuel valves FO-32, F.O. SPLY TO ENG, and FO-12, E.D.G. DAY TK FILL, located
in the emergency diesel generator room, are OPEN.
a.
In the emergency diesel generator room overhead outboard, open valves FO-32, F.O. SPLY TO ENG, and FO-12,
E.D.G. DAY TK FILL.
b.
At the emergency switchboard in the emergency diesel generator room, set the ENG. CONTROL SW (figure 14,
item 1) to the AUTO position.
c.
At the emergency diesel generator control panel in the emergency diesel generator room, complete the following
actions:
(1)
Turn the red START/STOP pushbutton (figure 18, item 1) clockwise to place it in the OUT position to
complete the starting circuit.
(2)
Set the RESET control switch (figure 18, item 2) to the AUTO START position.
WARNING
RESET
0
1
3
2
2
1
Figure 18. Emergency Diesel Generator Control Panel
END OF WORK PACKAGE