TM 55-1925-273-10-1
0074 00
4.
Energize and test the high level alarm panel:
a.
In the engine room on the aft bulkhead of the EOS, at the machinery DC control distribution panel, set/verify that
the FUEL OIL DAY TANKS (P&S) HIGH LEVEL ALARM circuit breaker (figure 4, item 1) is set to ON.
1
Figure 4. Machinery DC Control Distribution Panel
b.
In the engine room, at the fuel oil transfer station, test the port and starboard day tank high level alarm panel by
momentarily placing each TEST switch (figure 5, item 1) in the ON position.
c.
If necessary, secure the tested alarm by momentarily pressing the HORN/STROBE SILENCE pushbutton
(figure 5, item 2) on the port and starboard day tank high level alarm panel.
1
2
Figure 5. High Level Alarm Panel
0074 00-3


 