TM 55-1925-273-10-1
0078 00
2.
Fluid level monitoring procedures:
NOTE
The TLI panels in the EOS are the master transmitter modules. The repeaters are located in the
various spaces and are slaved to the transmitter modules. If there are disparities between the
transmitter and receiver, the transmitter is considered correct until proven otherwise.
a.
To monitor at a transmitter module, observe the fluid level meter (figure 2 & 3, item 3) to determine the correct
fluid level.
b.
To monitor at a receiver panel, locate the TLI of the tank to be monitored and observe fluid level meter (figure 4,
item 1) to determine the fluid level.
1
Figure 4. TLI Remote Indicator
3.
Alarm monitoring procedure:
NOTE
Only the port and starboard day tanks have alarms on the TLI system. The associated alarm will
sound only at the master TLI panel in the EOS. A LOW LEVEL alarm indicates that the tank is
at 25% or less capacity, and a HIGH LEVEL alarm indicates the tank is at 95% or greater
capacity.
a.
When the alarm speaker (figure 2, item 4) sounds on the 11 channel master TLI panel, observe the indicator lights
(figure 2, item 5 or 6) to determine the cause.
b.
Take appropriate action to correct the alarm condition.
0078 00-3


 