TM 55-1925-273-10-1
0080 00
2
1
3
Figure 18. ROWPU 24 Vdc Control Panel
7.
Verify that the general service system is online (WP 0071 00) and operating at a minimum pressure of 60 PSI (4.1 bar).
8.
Verify that the brominator is online and operating normally, or that PW-36, BYPASS-BROMINATOR (figure 19, item 1) is
OPEN.
9.
CLOSE RO-V-1 (figure 20, item 1), main sea water supply.
10. OPEN the following valves:
a.
RO-V-7 (figure 21, item 1), backflow preventer supply valve
b.
RO-V-6, (figure 21, item 2), backflow preventer discharge valve
c.
RO-V-9, (figure 22, item 1), fresh water flush pump supply valve
d.
RO-V-1-2 (figure 23, item 1), ROWPU 1 brine discharge valve
e.
RO-V-2-2 (figure 23, item 2), ROWPU 2 brine discharge valve
f.
RO-V-8 (figure 23, item 3), product water discharge valve
g.
PW-13 (figure 22, item 2), starboard potable water tank fill valve
h.
PW-12, POT. WTR. TK. PORT FILL (figure 22, item 3)
0080 00-16
|
||