Custom Search
 
  
 
TM 55-1925-273-10-1
0094 00
SHORE POWER CABLE DISCONNECTION
WARNING
Ensure that the power cable does not enter the water. Electrocution, serious injury, death
or equipment damage can occur during connecting or disconnecting if the cable connector
gets wet.
NOTE
Place all electronic and unnecessary electrical equipment in standby while shifting from shore
power to ship power. Ensure that the selected ship's service diesel generator is operating and
ready to accept an electrical load.
1.
On the main switchboard:
a.
Set the SHORE POWER CKT. BKR. (figure 2, item 4) to OFF.
b.
Quickly set the GENERATOR 1 CKT. BKR (figure 2, item 2) or GENERATOR 2 CKT. BKR. (figure 2, item 3) to
ON.
c.
Ensure that the MAIN SWBD BUS TIE CKT. BKR. OPEN indicator (figure 3, item 4) is illuminated.
2.
At the emergency switchboard:
a.
Set the ENGINE CONTROL SW. MAN. OFF AUTO. switch (figure 3, item 2) to the MAN. position.
b.
Push the MAIN SWBD BUS TIE CKT. BKR. OPEN pushbutton (figure 3, item 5) to the ON position.
c.
Ensure that the MAIN SWBD BUS TIE CKT. BKR. OPEN indicator (figure 3, item 4) is illuminated.
3.
At the dock shore power panel, set the power switch to OFF.
WARNING
Ensure that the electrical power switch is OFF at the dock shore power panel. Electrocu-
tion can result in serious injury or death.
4.
Remove the shore power cable at the dock shore power panel.
5.
Stop-off one end of the heaving line to the cable end at dockside.
0094 00-5


 