01 Level Fan Room
RFAC-59
RFAC-27
FAN
COIL
4
UNIT
RFAC-35
RFAC-57
RFAC-31
RFAC-22
RFAC-25
RFAC-34
1
RFAC-40
3
To A/C
2
Condensing Unit
Figure 4. 01 Level Fan Room Air Conditioning Refrigerant Valves
g.
RFAC-38, 4 COIL SUCT, COV R1-25-2 (figure 3, item 9), coil suction
h.
RFAC-42, 8 COIL SUCT COV, R1-25-2 (figure 3, item 10), coil suction
3.
In the 01 level AFT fan room, CLOSE the following valves:
a.
RFAC-31, EQL LINE (figure 4, item 1), TXV outlet
b.
RFAC-34, TXV COV, R01-32-2 (figure 4, item 2), TXV outlet
c.
RFAC-40, COIL SUCT COV, R01-32-2 (figure 4, item 3), coil suction
d.
RFAC-35, TXV COV,R01-32-2 (figure 4, item 4), TXV inlet
SECURE THE REEFER PLANT PIPING SYSTEM
1.
On the engine room aft bulkhead, CLOSE the following valves:
a.
RFSS-13, LIQUID LINE CRSVR COV (figure 5, item 1), liquid line crossover cut out
b.
RFSS-14, TXV/STNR/LLSV COV (figure 5, item 2), TXV strainer low-level suction
c.
RFSS-11, TXV/ STNR / LLSV COV (figure 5, item 3), TXV strainer low-level suction
d.
RFSS-8, TXV/ STNR / LLSV COV (figure 5, item 4), equalizing line
e.
RFSS-12, TXV / STNR / LLSV COV (figure 5, item 5), TXV strainer low-level suction
f.
RFSS-15, TXV/STNR/LLSV COV (figure 5, item 6), TXV strainer low-level suction